Category: True Online UPS Single phase
Model Name: Titan Elite G2-1.5kVA/1.35kW
Model Number: TE1500
     Download Brochure
Check Alarm Code
 Features
  - THE SUPERB PERFORMANCE SMALL UPS
  - DSP Control
  - 0.9 Output Power Factor
  - Wide Input Range 100-300VAC
  - High Efficiency 97% (ECO mode)
  - Frequency Converter Mode
  - Input THDI <5%
  - Output THDv <2% linear
  - Programmable LCD display
  - Extendable Run Time
  - Recharge to 90% battery capacity within 4 hrs.
  - Free Power Management Software
  - Optional SNMP & Relay Cards
  - Compact Design
  - Build-in Over Voltage Cut-Off device (OVCD) for tough environment
คลิกดูรายละเอียด OVCD
  - CE Declaration of Conformity
 

Product Descriptions

TE-G2 Series UPS make use of the unique True Online Double Conversion circuitry to detect the electricity current and voltage output of utility power supply. The current is input via high frequency PWM to maintain uniform wave form and phase in line with the voltage, so as to attain high input power factor over to 0.99 and avoid generating comparatively significant harmonic interference on the power network.
With the use of the outstanding IGBT as the power convertion component, the operating frequency of the Inverter of UPS is capable of reaching tens of KHz, due to the high frequency operating characteristics of IGBT. Higher working efficiency of the inverter also improves the overall efficiency of UPS and higher inversion frequency reduces the noise of the inverter as well. Due to its components margins are increased.
*คลิกดูเทคนิค True Online Double Conversion

TypeItemsSpecification
CapacityCapacity1500VA/1350W
InputVoltage Range100 (+/-3%) ~ 300 (+/-3%) VAC
 Frequency Range50 +/- 10% Hz
 PhaseSingle Phase with Ground
 Current THDI<5%
 Power Factor>= 0.99
 Generator InputSupport (2.2 x UPS Rating Power)
OutputVoltage Range220 +/- 1% VAC
 Frequency Range50 +/- 0.1% Hz
 Crest Factor3:1
 Harmonic Distortion< 2% THD (Linear Load)
 Output Wave formPure Sine Wave
 OutletUniversal 4 outlets
 Overload Capacity1 min @ 105%~130% ; 10 sec @ 130% ~ 150% ; 300ms @ >150%
 Redundancy (Option)Dual Modular Redundant (DMR)
EfficiencyAC mode>89%
 Battery Mode>84%
 ECO>97.2%
BatteryNumber of Battery2 pcs. or on requested
 Battery type12V/(7/9)Ahr (Sealed Lead-Acid Maintenance Free with suspended electrolyte) or on requested
 Backup time> 5 mins depend on load
 Recharge Time (to 90%)4 hrs.
Transfer TimeTransfer Time0 ms.
IndicatorLCD versionLoad, Battery, Input, Output, Operation Mode Information
Audible AlarmBattery ModeSounding every 4 seconds
 Low BatterySounding every second
 OverloadSounding twice every second
 FaultContinuously Sounding
DimensionTower Case (WxHxD)mm144x229x345
WeightTower Case (kgs)9.4
EnvironmentOperation Environment0-40 C
 Relative Humidity0-95% (Non-Condensing)
 Noise Level<45dB @ 1 Meter
InterfaceSmart RS-232 / USB (Option)S/W supports Windows Family, Linux, Sun Solaris, IBM AIX, Compaq True64, SGI IRIX, FreeBSD, HP-UX and MAC
 External Slot (Option)Internal Type of SNMP / AS400 Relay Card / RS485
International Standard CEESD: IEC61000-4-2 Level 3, RS:IEC61000-4-3 Level 3, EFT:IEC61000-4-4 Level4, Surge:IEC61000-4-5 Level 4, Conduction:IEC62040-2 Cat C2, Radiation:IEC62040-2 Cat C2 Transportaion: Drop:ISTA 2A, Vibration:internal standard, Protection: IP20 (static)