| Type | Items | Specification | 
	
		| Capacity | Power rating | 100 kVA/90 kW | 
	
		| Input | Topology | PWM, IGBT based | 
	
		|   | Rated voltage | 380Vac/220Vac (400/415Vac selectable) | 
	
		|   | Voltage range | -45% ~ +25%, depends on load percentage | 
	
		|   | Input power factor | 0.99 | 
	
		|   | THD(i) | <3% | 
	
		|   | Rated Frequency | 50/60Hz auto sensing | 
	
		|   | Frequency range | 42-72Hz | 
	
		| Output | Power factor | 0.9 | 
	
		|   | Efficiency | Up to 94% in online mode;>98% in ECO mode | 
	
		|   | Voltage | 380Vac/220Vac+/-1%(400/415Vac selectable) | 
	
		|   | Frequency | 50/60Hz | 
	
		|   | Overload capacity | <105% continuous; 105%-125% 10min; 150% 1min | 
	
		|   | THDV | <2% for Linear load | 
	
		|   | Unbalanced load | 100% | 
	
		|   | Crest factor | 3:1 | 
	
		| Bypass                                             | Internal static switch | Standard | 
	
		|   | Bypass voltage | 380Vac(+/-15%) | 
	
		|   | Maintenance bypass switch | Standard | 
	
		| Battery | Battery type | VRLA | 
	
		|   | Backup time | Varies from battery capacity and load situation | 
	
		|   | Battery PCS | 36-40 PCS adjustable, 40 PCS as default | 
	
		|   | Recharge time | 8 hours to 90% | 
	
		| Dimension | WxDxH (mm) | 600x800x1876 | 
	
		| Environment | Running temperature | UPS:0-40 C; Battery: 25 C | 
	
		|   | Storage | -25~55 C without battery; +15~25 C with battery | 
	
		|   | Humidity | 5%~95% | 
	
		|   | Elevation | No derating < 1000m | 
	
		|   | Noise level | <= 65 dBA@1 meter front side | 
	
		| Interface | Interface | RS232,USB,2 Com slots,3 Building alarm,EPO | 
	
		|   | Com cards(optional) | SNMP/WEB, Modbus/Ethernet, AS400, NMC | 
	
		| International Standard                             | Safety | IEC/EN 62040-1 | 
	
		|   | EMC | IEC/EN 62040-2 | 
	
		|   | Performance | IEC/EN 62040-4 | 
	
		|   | Quality | ISO9001,ISO14001 | 
	
		|   | Certification | CE |