Type | Items | Specification |
Capacity | Power rating | 80 kVA/72 kW |
Input | Topology | PWM, IGBT based |
| Rated voltage | 380Vac/220Vac (400/415Vac selectable) |
| Voltage range | -45% ~ +25%, depends on load percentage |
| Input power factor | 0.99 |
| THD(i) | <3% |
| Rated Frequency | 50/60Hz auto sensing |
| Frequency range | 42-72Hz |
Output | Power factor | 0.9 |
| Efficiency | Up to 94% in online mode;>98% in ECO mode |
| Voltage | 380Vac/220Vac+/-1%(400/415Vac selectable) |
| Frequency | 50/60Hz |
| Overload capacity | <105% continuous; 105%-125% 10min; 150% 1min |
| THDV | <2% for Linear load |
| Unbalanced load | 100% |
| Crest factor | 3:1 |
Bypass | Internal static switch | Standard |
| Bypass voltage | 380Vac(+/-15%) |
| Maintenance bypass switch | Standard |
Battery | Battery type | VRLA |
| Backup time | Varies from battery capacity and load situation |
| Battery PCS | 28-36 PCS adjustable, 32 PCS as default |
| Recharge time | 8 hours to 90% |
Dimension | WxDxH (mm) | 600x720x1200 |
Environment | Running temperature | UPS:0-40 C; Battery: 25 C |
| Storage | -25~55 C without battery; +15~25 C with battery |
| Humidity | 5%~95% |
| Elevation | No derating < 1000m |
| Noise level | <= 65 dBA@1 meter front side |
Interface | Interface | RS232,USB,2 Com slots,3 Building alarm,EPO |
| Com cards(optional) | SNMP/WEB, Modbus/Ethernet, AS400, NMC |
International Standard | Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Performance | IEC/EN 62040-4 |
| Quality | ISO9001,ISO14001 |
| Certification | CE |