Category: Line Interactive Pure Sine Wave
Model Name: Radian 1000
Model Number: RD1000
     Download Brochure
Check Alarm Code
 Features
  - Line Interactive with Stabilizer Design
  - 100% Digitized Microprocessor Controlled
  - Pure Sine Wave Output
  - Automatic Voltage Reguration (+/-25%)
  - Two in one design: Tower & Rack 19" case
  - Network Transient Protector guards your network communications equipment from surges.
  - DC Start (Power On UPS w/o line input utility)
  - Short Circuit, Overload & Surge Protection
  - Built-in Dry contact/RS-232/USB communication port
  - Free of charge "WinPower" monitoring & controll S/W via LAN/WAN
  - SNMP adaptor with "UPSnodeManger" via SNMP protocal
  - MIB II standard for SNMP node management S/W
  - Hot Swappable Battery
  - CE Declaration of Conformity
 

Product Descriptions

Radian series of line interactive UPS provides pure sine wave AC output with better harmonic distortion than traditional line interactive UPS in step wave output. Radian series is available for 500VA, 750VA, 1000VA, 1500VA capacity. For data center with Rack mount demand, you can adapt the optional rack kit to install the Radious 1000VA & 1500VA in 19” rack. This series provides you satisfying reliable performance and maximize the flexibility for your system integration.SmartPower "Your Smart Choice for UPS".
*คลิกดูเทคนิค Line interactive pure sine wave

TypeItemsSpecification
CapacityCapacity1000VA/600W
InputVoltage Range220 + 25% -23%VAC
 Frequency Range50 +/- 10% Hz
 PhaseSingle Phase with Ground
 Generator InputSupport
OutputVoltage Range220 +/- 10% VAC
 Voltage Range (Batt.Mode)220 +/- 10% RMS for entire battery voltage range
 Frequency Range50 +/- 0.1% Hz
 Output Wave formPure Sine Wave
 OutletNEMA x 6
Overload Rating Line Mode110% shutdown after 3 minute; 130% shutdown after 10 cycles.
 Battery Mode110% shutdown after 30 sec.;120% shutdown after 5 cycles.
BatteryBattery type12V/7A (Sealed Lead-Acid Maintenance Free with suspended electrolyte) or on requested
 Number of Battery2 pcs. or on requested
 50% load backup time11 minutes
 1 PC backup time (typical)35 minutes
 Battery hot swapYES
 Battery ProtectionBattery Overcharges/Battery deep discharge/Auto self test/Fan failure protection
 Recharge Time< 6 hrs to 90%
Transfer TimeTransfer Time2 ms.
IndicatorLED displayUPS status, Load Level, Battery Level, Fault
Audible AlarmBattery ModeSounding every 10 seconds
 Low BatterySounding every second
 UPS FaultContinuously Sounding
 OverloadSounding every 0.5 second
 Battery ReplacementSounding every 3 second
 Over chargeSounding every 1.5 seconds
 Over termperatureSounding every 2.5 seconds
 Charger failSounding every 3 seconds
DimensionTower Case (LxWxH)mm390x86x328 mm
WeightTower Case (kgs)9.8
EnvironmentOperation Environment0-40 C
 Relative Humidity0-90% (Non-Condensing)
 Noise Level<40dB @ 1 Meter
InterfaceSmart RS-232 / USBS/W supports Windows Family, Linux, Sun Solaris, IBM AIX, Compaq True64, SGI IRIX, FreeBSD, HP-UX and MAC
 External Slot (Option)External Type of SNMP
International Standard CELow Voltage Directive(Safety): EN62040-1-1, EMC Directive: EN62040-2 C2,EN62040-2,EN61000-3-2