Type | Items | Specification |
Capacity | Power rating | 25-200kVA, pf 1.0 |
Input | Topology | Double convertion online technology,three-level bridge IGBT PWM control |
| Rated voltage | 3ph+N+PE |
| Voltage range | 220/380,230/400,240/415V |
| Input power factor | 0.99 @ 100% load |
| THD(i) | <3% |
| Rated Frequency | 50/60Hz user configurable |
| Frequency range | 40-72Hz |
| Soft start capability | Yes |
Output | Power factor | 1 |
| Efficiency | Up to 96% in online mode;>99% in ECO mode |
| Voltage | 230/400Vac nominal(220/380, 240/415 Selectable) |
| Frequency | 50/60Hz |
| Overload capacity | 20KS-80KS model: 102110% load 60 min, 111125% load 10min, 126150% load 1min, >150% load 150msec
*20-80K battery kit model and STD internal battery model: depends on battery configuration. |
| THDV | <2% for Linear load |
Bypass | Internal static switch | Standard |
| Bypass voltage | 400Vac(+/-15%) |
| Maintenance bypass switch | Standard |
Battery | Battery type | VRLA/Lithium. |
| Backup time | 20KS-80KS model: Varies from battery capacity and load situation. 20-80K battery kit model: Depends on battery configuration. 20-80K STD internal battery model: 3.5mins @ 100% load |
| Battery PCS | 36 to 42 blocks. Default is 40 blocks |
| Charger method | Optimized Battery Management or Continuous Float charging |
Dimension | Cabinet dimensions (WxDxH) | 75kVA Without Battery Cabinet : 600 x 1100 ? 2020 mm 75kVA With Battery Cabinet : 600 x 1100 ? 2020 mm 200kVA Cabinet : 603 x 1013 x 2050 mm UPM : 439 ? 595 x 130 mm Battery Module : 107 ? 900 ? 156 mm |
Weight | Insalled weight | 75kVA Without Battery Cabinet : 262 kg 75kVA With Battery Cabinet : 336 kg 200kVA Cabinet : 368 kg UPM : 27.5 kg Battery Module : 31 kg |
Environment | Humidity | 5%~95% |
| Altitude (max) | 1000m above sea level at 40?C |
| Noise @1m, 25 c | < 70 dBA in double conversion |
Communication | Interface | 3 communication Slots, Built-in host and device USB, 5 building alarm inputs and a dedicated EPO |
| Com cards(optional) | NMC & CMC cards, relay card, EMP |
International Standard | Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Performance | IEC/EN 62040-3 |
| RoHS | EU directive 2011/65/EU |
| Quality | ISO9001,ISO14001 |
| Certification | CE |